Fire Extinguisher Monthly Inspection Checklist

Portable Fire Extinguishers20 inspection itemsUpdated 2026-09-01

Print-ready PDF

Download this checklist as a print-ready PDF, available in 4 languages.

Why this inspection matters#

NFPA 10 and OSHA 29 CFR 1910.157(e)(2) require every portable fire extinguisher to be visually inspected at least monthly. A non-working extinguisher in a fire is worse than no extinguisher at all — it delays evacuation while people fight a fire that won't go out.

The monthly check is a quick visual confirmation that the extinguisher is where it belongs, accessible (1910.157(c)(1)), fully charged, sealed, and undamaged; any trained employee can perform it, and it takes under a minute. It does not replace the deeper service tiers, which OSHA defers to NFPA 10 for: annual maintenance by a qualified technician, a 6-year internal examination for stored-pressure dry-chemical units, and hydrostatic testing at 5- or 12-year intervals depending on type (1910.157(e)(3) requires maintenance per the manufacturer and NFPA 10). Records of the monthly check are kept on the tag; annual-maintenance records are retained at least a year.

Any FAIL means the unit is tagged out of service and a charged replacement is put in its place immediately.

How to use this checklist#

Fill in the date, inspector, location, and equipment ID. Check each item Pass, Fail, or N/A, recording specifics in the notes column. Item 18 (wheeled units) is N/A for handheld extinguishers. When the check passes, initial and date the tag; any defect tags the unit out and triggers a replacement. The inspection is signed by the inspector and countersigned by the supervisor.

Fire extinguisher monthly inspection items#

#Inspection itemPassFailN/ANotes
1Extinguisher is in its designated location and clearly visible.☐☐☐
2Path to the extinguisher is unobstructed and at least 36 inches wide.☐☐☐
3Mounting bracket or cabinet is intact and secure on the wall.☐☐☐
4Mounting height is correct: top no higher than 5 feet above the floor (60 inches).☐☐☐
5Signage above or near the extinguisher is visible from a distance.☐☐☐
6Pressure gauge needle is in the green operable zone (not low or overcharged).☐☐☐
7Tamper seal on the pull pin is intact and unbroken.☐☐☐
8Pull pin is in place and not bent or damaged.☐☐☐
9Hose or nozzle is unobstructed, free of cracks, and not blocked.☐☐☐
10Body of the extinguisher shows no dents, rust, corrosion, or damage.☐☐☐
11Discharge nozzle has no powder, foam residue, or debris in the opening.☐☐☐
12Inspection tag is attached, current, and shows last service and inspection dates.☐☐☐
136-year internal maintenance and 12-year hydrostatic test dates are current (per NFPA 10).☐☐☐
14Operating instructions on the label are legible and face outward.☐☐☐
15Class rating (A, B, C, D, K) matches the hazards in the area where it is mounted.☐☐☐
16Extinguisher type and size match the protected occupancy and travel-distance rule.☐☐☐
17Extinguisher feels properly weighted (not significantly lighter than expected).☐☐☐
18For wheeled units: wheels turn freely; chassis and handles are intact.☐☐☐
19Inspector has signed and dated the tag for this monthly inspection.☐☐☐
20Any defect found has been reported, the unit tagged out, and a replacement provided.☐☐☐

Corrective actions taken#

Describe any issues found and the steps taken to correct them. A defective or discharged extinguisher is tagged out of service and replaced with a charged unit immediately — never left in place "until it can be serviced."

Inspection sign-off#

  • Inspector signature: __________________________
  • Supervisor signature: __________________________
  • Inspection result: ☐ All items passed ☐ Issues require follow-up

Disclaimer#

This checklist is a general guide based on OSHA 29 CFR 1910.157 and NFPA 10. Always follow your site-specific procedures, the manufacturer's instructions, and the service intervals NFPA 10 sets for your extinguisher type.